COMPUCOOL Quick Disconnect UQD Series
DN6-DN12 | Flat Anti-Drip | Push-In/Threaded
Hand-plug liquid cooling quick connectors for server nodes and cold plate maintenance. Dual-end flat valve cores seal the flow path instantly upon disconnection to minimize fluid leakage and air ingress. Available with push-to-lock or threaded locking connection methods. Valve body made of stainless steel; seals selected for deionized water or ethylene glycol solutions. Designed to integrate seamlessly with manifolds and cold plates.
Parameters are subject to the manufacturer's sample and final solution confirmation.
Core Features
Flat valve core with double-ended self-sealing; no visible dripping upon disconnection.
Push-to-lock or thread-lock with a clear tactile connection
304/31 6L Stainless Steel Valve Body, Compatible with Deionized Water and Ethylene Glycol
DN6-DN12 bore coverage, balancing node and cold plate circuits.
Color-coded to distinguish inlet and return lines
Dust cap and mounting bracket are optional.
Individual airtightness test at factory
Detailed Specifications
| Nominal Diameter | DN6 / DN8 / DN12 |
|---|---|
| Connection Method | Push-lock / Thread-lock |
| Valve Body Material | 304 / 316L Stainless Steel |
| Sealing material | EPDM / Fluoroelastomer |
| Work stress | 1.0MPa (small bore can be as small as 1.6MPa) |
| Burst Pressure | ≥4.0MPa |
| Operating Temperature | -20~120℃ |
| Insertion/Extraction Cycles | ≥10000 times |
| Off | No visible dripping |
| Applicable Media | Deionized water / Ethylene glycol solution |
| Anti-misconnect | Color Coding |
| Attachment | Dust Cap / Mounting Bracket |
Application Areas
ConfirmCOMPUCOOL Liquid Cooling Quick Disconnects UQD Seriesconfiguration?
Provide operating conditions, media type, and installation requirements—we'll help confirm the series, connections, and spare parts.